Soundness Test of Cement as per Indian Standard (IS 4031: Part 3)
- Get link
- X
- Other Apps
Soundness Test of Cement as per Indian Standard (IS 4031: Part 3)
Aim
To determine the soundness of cement by using the Le-Chatelier method and ensure that the cement does not undergo excessive expansion after setting.
Apparatus
- Le-Chatelier Mould: A split cylinder of brass with two indicators attached at the top.
- Weighing Balance: Accurate to 0.1 g.
- Water Bath: Maintains a temperature of 27°C ± 2°C.
- Vernier Caliper: To measure the distance between the indicators of the Le-Chatelier mould.
- Measuring Cylinder: For measuring water.
- Trowel: For mixing.
Theory
The soundness of cement refers to its ability to retain volume stability after setting. Unsound cement may expand excessively, leading to cracks and loss of structural integrity. The primary causes of unsoundness are the presence of free lime (CaO) and magnesia (MgO) in cement, which can hydrate and expand after the cement has set. The soundness test helps determine whether cement will undergo excessive expansion after hardening, ensuring its long-term durability.
The Le-Chatelier method measures the expansion of cement by placing a paste in the Le-Chatelier mould, immersing it in water, and observing the distance between the indicators before and after heating.
Procedure
Preparation of Cement Paste:
- Take 100 g of cement and mix it with the required amount of water (approximately 0.78 times the standard consistency) to form a cement paste.
- Fill the Le-Chatelier mould with the cement paste, ensuring it is compacted without any air voids.
Initial Measurement:
- After filling the mould, close the split ends with glass plates and immerse the mould in water at room temperature.
- Measure the initial distance between the two indicators using a vernier caliper.
Boiling:
- Keep the mould in the water bath and maintain the temperature at 27°C ± 2°C for 24 hours.
- After 24 hours, heat the water to boiling and maintain it at boiling temperature for 3 hours.
- Allow the mould to cool gradually to room temperature.
Final Measurement:
- Measure the distance between the indicators again using the vernier caliper after cooling.
Observation Table
Sample No. | Initial Distance (mm) | Final Distance (mm) | Expansion (mm) |
---|---|---|---|
1 | 10.2 | 11.5 | 1.3 |
2 | 10.0 | 11.4 | 1.4 |
3 | 10.1 | 11.6 | 1.5 |
Sample Readings
- Initial Distance: 10.2 mm
- Final Distance: 11.5 mm
- Expansion = Final Distance - Initial Distance Expansion=11.5mm−10.2mm=1.3mm
Reporting the Results
The soundness of cement is the expansion value calculated by the difference between the initial and final distance of the indicators. As per Indian Standards, the allowable limit for expansion is 10 mm for Ordinary Portland Cement (OPC).
In this test:
- Expansion for Sample 1 = 1.3 mm
- Expansion for Sample 2 = 1.4 mm
- Expansion for Sample 3 = 1.5 mm
All results are within the permissible limits specified by IS 4031.
Conclusion
The soundness test indicates that the cement used in this test does not undergo excessive expansion after setting. The maximum observed expansion is 1.5 mm, which is well below the permissible limit of 10 mm. Therefore, the cement is considered sound and fit for construction use. This ensures that the cement will not lead to cracking or structural issues due to expansion after setting.